Temperature Ratings and Model Numbers (Use Linear Detector of Proper Temperature Rating)
Regular Intermediate High Extra High
Alarm Temperature 155°F (68°C) 190°F (88°C)/220°F (105°C) 280°F (138°C) 356°F (180°C)
Max. Installed
Up to 100°F(38°C)
190 Up to 150°F (66°C)
Up to 200°F (93°C)
Up to 221°F (105°C)
Ambient Temp. 220 Up to 175°F (79°C) EPR Up to 250°F (121°C)
Multi-purpose/ PHSC-155-EPC PHSC-190-EPC PHSC-280-EPC PHSC-356-EPC*
知名GSC-03-21441-00戈尔电缆出售_矿用电缆相关-上海道夫自动化仪表工程有限公司
Industrial PHSC-220-EPC1
Abrasion/Limited PHSC-155-EPR PHSC-190-EPR PHSC-280-EPR PHSC-356-EPR*
Chemical Resistance PHSC-190-EPN
MODEL NO. PHSC-6893-TRI Dual Temperature Detector (TRI-Wire™)
All Protectowire models can be supplied on Messenger Wire. Add suffix “-M” to above model numbers. *FM Approved for special application use only. 1FM Approved Only.
Approvals/Maximum Listed Spacing
Type EPC Type EPN Type EPR Type TRI
UL (25 ft./7.6m) UL (25 ft./7.6m) UL (25 ft./7.6m)
FM (25 ft./7.6m) FM (25 ft./7.6m) FM (25 ft./7.6m) FM (15 ft./4.6m)
Max. Installed Ambient Temp. = 100°F (38°C); Low Temp. Pre-alarm = 155°F (68°C); High Temp. Alarm = 200
正规GSC-03-21441-00戈尔电缆制造商_哪里有轨道交通设备器材-上海道夫自动化仪表工程有限公司